SKAT-100C
Dielectric test apparatus
The device is designed for testing and diagnosing the insulation of power cables, surge arresters, solid dielectrics, protective equipment and other objects and materials that require high voltage testing. It can also be used as a high voltage alternating and direct current generator.
The device is available in two versions:
SKAT-100CPrice 435 000₽ WITHOUT VAT
SKAT-100C-S Price 450 000₽ WITHOUT VAT
The device has a bright six-inch LCD display with a detailed display of all the main and additional test parameters (rms value of current and voltage, peak voltage value, average value of the output current, output power, leakage current for 10 seconds).
The device SKAT-100C has extended functionality. In addition to the manual and automatic modes, a test mode according to built-in programs is implemented — the device will automatically pick up the specified voltage at the rate specified in the program, withstand the specified time, relieve the voltage and display a full report on the screen. The parameters and names of 10 programs can be edited using the user menu. Reports of the last 50 tests are stored in non-volatile memory and are available for viewing and printing using a printer connected via RS232 (optional). There is a real time clock.
There is an automatic mode of preliminary burning of defective insulation. This mode is used for insulation breakdown in couplings and for floating breakdowns to reduce the breakdown voltage to the level of the operating voltage of the burners. This mode can also be used to charge capacitors in acoustic shock wave generators.
SKAT-100C has a version of the control unit in a case.
Execution of the high-voltage block in the steel case.
SKT-100C‑S is designed as a control unit in a metal case for rack mounting.
Execution of the high-voltage block in the steel case.
DC voltage test | Output voltage | Regulation range, kV | from 1 to 101 |
Measurement range, kV | from 3 to 100 | ||
Limits of permissible relative measurement error, % |
± (2,0+0,04·((100/U)-1)),where U - measured value, кВ |
||
Pulsation amplitude, % | 3 | ||
DC voltage polarity | negative (positive optional) | ||
Output current | Maximum level, mA | 15 | |
Measurement range, mA | from 0,1 to 15 | ||
Limits of permissible relative measurement error, % | ± (2,0+0,1·((15/I-1)), where
I - measured value, мА |
||
Alternating current (AC) test | Output voltage | Regulation range, kV | from 1 to 71 |
Measurement range, kV | from 3 to 70 | ||
Limits of permissible relative measurement error, % | ± (2,0+0,04·(70/U)-1)), U - measured value, кВ | ||
Pulsation amplitude, % | 5 | ||
Output current | Maximum level, mA | 35 | |
Measurement range, mA | от 0,1 до 35 | ||
Limits of permissible relative measurement error, % | ± (2,0+0,1·((35/I-1)), I - measured value, mA | ||
Load capacity at maximum voltage | up to 2.5 nF | ||
System Settings | Test Modes |
■ Manual ■ Automatic ■ According to the program |
|
Voltage change rate, kV/s | 0,5; 1; 2; 5 | ||
Interfaces | Indication | 6" LCD display | |
Device management | Pushbutton and encoder | ||
Safety | Grounding |
■ Protective earth ■ Automatic earthing switch |
|
Protection |
■ Overvoltage and current protection ■ Shutdown in the event of a breakdown in the load ■ High voltage unit overheating protection ■ External signal lamp (option) |
||
High voltage disconnect systems |
■ Emergency stop button ■ Security lock (option) |
||
Power and Consumption Options | AC supply voltage, V | from 198 to 242 | |
Power supply frequency, Hz | from 49 to 51 | ||
Maximum power consumption | 2800 В•А | ||
Maximum current consumption, A | 15 |
Control block | SKAT-100C | SKAT-100C-S |
Height, mm | 420 | 180 |
Width, mm | 340 | 450 |
Length, mm | 220 | 300 |
Weight, kg | 14 | 17,5 |
High voltage block | SKAT-100C | SKAT-100C-S |
Height, mm | 1020 | |
Width, mm | 420 | |
Length, mm | 650 | |
Weight, kg | 80 |